RENEWIOSITY Engineering · Interactive learning tools

Grid Integration Technology Toolbox

Nine calculation modules connecting renewable generation, power systems and grid engineering. Explore governing assumptions, inspect interactive charts and export preliminary screening results.

v1.2.1 · Branded exports
Local browser calculations · No user data uploaded
01 · Choose a moduleStart with theory or select one of nine engineering calculators.
02 · Enter assumptionsUse the stated units, calculate and explore the sensitivity charts.
03 · Verify before applyingThese are educational screening models, not certified engineering designs.

Grid Integration Theory

Fundamental definitions and governing expressions used across the tool.

Model boundary. Definitions and equations provide context for the simplified models. Read the module-specific assumptions before interpreting numerical results.

Key Term Definitions

Point of Common Coupling (PCC)
The interface point between the distributed energy resource (DER) and the utility grid, where voltage quality and protection are assessed.
Capacity Factor (CF)
Ratio of actual energy produced over a period to the energy that would have been produced at full rated power for the same period.
Penetration Level
The share of renewable or DER generation relative to total system load or generation capacity, usually expressed as a percentage.
Capacity Credit
The amount of reliable peak-load capacity a DER can displace from conventional generation while maintaining the same loss-of-load probability.
Curtailment
Reduction of renewable generator output below its available potential, typically due to grid constraints, oversupply, or stability limits.
Ramp Rate
The rate of change of active power output (MW/min), a key grid-code requirement for integrating variable renewable energy (VRE).
RoCoF (Rate of Change of Frequency)
How fast system frequency changes after a disturbance, df/dt, inversely proportional to system inertia.
Frequency Nadir
The lowest (or highest) frequency point reached after a contingency before primary frequency control arrests the decline.
Inertia Constant (H)
Stored kinetic energy in synchronous rotating mass per unit of generator MVA base, expressed in seconds.
Short Circuit Ratio (SCR)
Ratio of short-circuit capacity at the PCC to the rated power of the connected converter/plant; a measure of grid strength.
Total Harmonic Distortion (THD)
The square root of the sum of squares of all harmonic components relative to the fundamental component.
Voltage Flicker
Perceived fluctuation of lamp brightness caused by rapid, repetitive voltage variations, typically from fluctuating loads or wind farms.
LVRT / HVRT
Low-/High-Voltage Ride-Through: the ability of a generator to remain connected during grid voltage sags or swells per grid code.
Islanding
A condition where a DER continues to energize a section of the grid that has been de-energized by the utility; prevented by anti-islanding protection.
Power Factor (PF)
Ratio of real power to apparent power, PF = cos(φ), indicating how effectively electrical power is converted to useful work.
Fault Level
The maximum prospective short-circuit current (or MVA) at a point on the network, used for switchgear and protection coordination.

Governing Expressions

Capacity Factor
CF = Eactual / (Prated × t) × 100%
Penetration Level
Penetration = Prenewable / Pload × 100%
Wind Power Output
Pwind = ½ ρ A v³ Cp η (subject to turbine cut-in, cut-out and rating)
Solar PV Output
PAC = min[Pinverter rated, G A ηmodule (1 + γ ΔT) ηinv / 1000] (kW)
Battery Energy
EAC, available = Erated max[0, SOC − (1 − DoD)] √ηRT
Rate of Change of Frequency
RoCoFinitial = −ΔP × fnominal / (2 H Sbase) [Hz/s]
Aggregate Swing Equation
2H (1/fnominal) df/dt = ΔPmech,pu − ΔPloss,pu − D Δf/fnominal
Short Circuit Ratio
SCR = Sshort circuit / Splant rated (same apparent-power units)
Voltage THD
THDV = √(Σ Vh²) / V₁ × 100%
Current THD
THDI = √(Σ Ih²) / I₁ × 100%
Power Factor
PF = P / S = cos φ (sinusoidal fundamental conditions)
Voltage Drop (feeder)
ΔVLL ≈ √3 I (R cos φ + X sin φ) [balanced 3-phase]
Short Circuit Current
I3φ fault ≈ VLL / (√3 |Zequivalent|)

Solar PV Integration

Interactive engineering screening calculator with assumptions and sensitivity charts.

Model boundary. Screening scope: fixed irradiance and cell temperature, constant efficiency and inverter clipping. Not a time-series yield model.

Input Parameters

W/m² (STC = 1000)
m²
fraction (20%)
fraction (96%)
°C
°C (STC)
1/°C (typ. −0.004)
kW
hours

Results

Click "Calculate" to compute results.

Wind Power Integration

Interactive engineering screening calculator with assumptions and sensitivity charts.

Model boundary. Screening scope: cubic aerodynamic approximation and rated-power cap. Not a manufacturer-certified turbine power curve.

Input Parameters

m/s
m/s
m/s
m/s
kW
kg/m³
m
Betz limit ≤ 0.593
fraction
hours/year

Results

Click "Calculate" to compute results.

Battery Energy Storage (BESS)

Interactive engineering screening calculator with assumptions and sensitivity charts.

Model boundary. Screening scope: SOC window, assumed symmetric efficiency losses and simple energy throughput. Not a degradation or dispatch optimizer.

Input Parameters

MW
MWh
fraction (50%)
fraction (90%)
fraction
MW
hours
$/kWh
fraction
cycles

Results

Click "Calculate" to compute results.

Grid Interconnection

Interactive engineering screening calculator with assumptions and sensitivity charts.

Model boundary. Screening scope: balanced three-phase feeder, approximate transformer impedance and stiff upstream source. Not a short-circuit study.

Input Parameters

kVA
kV
kV
% on rated base
km
Ω/km
Ω/km
A
lagging
kV

Results

Click "Calculate" to compute results.

Power Quality

Interactive engineering screening calculator with assumptions and sensitivity charts.

Model boundary. Screening scope: partial THD from four selected harmonic orders. No standards compliance conclusion is possible.

Input Parameters

V (LL RMS)
A RMS
% of V₁
% of V₁
% of V₁
% of V₁
% of I₁
% of I₁
% of I₁
% of I₁

Results

Click "Calculate" to compute results.

Grid Stability

Interactive engineering screening calculator with assumptions and sensitivity charts.

Model boundary. Screening scope: aggregate single-area inertia, delayed static droop and load damping. Not a dynamic grid model.

Input Parameters

seconds
MVA
MW (loss of generation)
Hz/pu (5%)
Hz (±)
seconds
pu on system base
seconds
seconds
Hz

Results

Click "Calculate" to compute results.

Hydrogen Electrolyzer

Interactive engineering screening calculator with assumptions and sensitivity charts.

Model boundary. Screening scope: grid-limited production and electricity-only margin with simplified SEC degradation. Not a hydrogen LCOH model.

Input Parameters

MW
kWh/kg H₂
hours
$/kWh
$/kg
% per 1000 h
% of rated
MW
fraction

Results

Click "Calculate" to compute results.

EV Charging Load

Interactive engineering screening calculator with assumptions and sensitivity charts.

Model boundary. Screening scope: charger diversity, conservative transformer loading and battery-energy needs. Not an EV scheduling optimizer.

Input Parameters

vehicles
kW (Level 2)
hours
fraction (simultaneous)
ratio
kVA
kV (LV)
3-phase
0–1 (lagging assumed)
hour
hour (next day)
kWh
fraction (0–1)
fraction
grid to battery fraction

Results

Click "Calculate" to compute results.

Microgrid Protection

Interactive engineering screening calculator with assumptions and sensitivity charts.

Model boundary. Screening scope: fault-current magnitude sum and inverse-time curve illustration. Not a protection-coordination study.

Input Parameters

kA (3-phase)
kA
kA
A (primary)
TMS
Ω/km
km
:5 (primary:secondary)
seconds
kV
IEC standard
exponent

Results

Click "Calculate" to compute results.